TM 9-6115-663-13&P
Table 2-2. Operator Preventive Maintenance Check and services
for AN/MJQ-41, PU-805, and PU-806 (continued)
Location
Not Fully Mission
Item
Procedure
Capable if:
No.
Item to Check/Service
Interval
WARNING
NEVER attempt to start the generator set when it is not properly grounded.
Personal injury or death due to electrocution could result.
GENERATOR SET
Continued
Cable is missing or
GROUND ROD CABLE AND Inspect ground rod and cable for
Before
31
loose connections, breaks, damage, damaged.
CONNECTIONS
and corrosion.
Cables are
Ensure cables are properly
Before
INPUT LOAD AND
32
installed Inspect for damage and improperly installed,
PARALLELING CABLES
or damaged.
cutting.
Inspect output connectors for
Before
OUTPUT CONNECTORS
33
missing hardware or damage.