5. Attach lifting equipment (2) with a minimum lifting capacity of 6000 lb as shown in figure 5-10.
6. Insert ropes (10) through each of four lifting rings (8) on the generator set as shown in figure 5-10.
7. With one person at each rope (10) to steady and guide generator set (9), lift generator set.
INSTALLATION
WARNING
When lifting the generator set, use lifting equipment with a minimum
lifting capacity of 6000 lb. Do not stand under the generator set while it
is being lifted. Do not permit generator set to swing. Failure to observe
this warning can result in severe personal injury or death.
1. Attach lifting equipment (2) with a minimum lifting capacity of 6000 lb as shown in figure 5-10.
2. Insert rope (10) through four lifting rings (8) on generator set (9).
3. With one person at each rope (10) to steady and guide the generator set (9), lift the generator set.
4. Guide generator set skids into position on the trailer and lower generator set onto trailer.
NOTE
Step 5 applies to all generator sets.
5. For PU-801A generator set, install four screws (6), eight flat washers (7), four lock washers, and
plain nuts (6). For all other units, install four screws (1), eight flat washers (7), and four new self-
locking nuts (6) that secure generator set (9).
5-14.1/(5-14.2 Blank)
Change 3

Privacy Statement - Press Release - Copyright Information. - Contact Us