TM 9-2320-391-10
ELECTRICAL SYSTEM TROUBLESHOOTING - Continued 0069 00
ELECTRICAL SYSTEM Continued
Table 5. Electrical System Troubleshooting Procedures Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
120. M1079A1 110 VAC
3. Check circuit breaker
1. Open door on 110/208 VAC
OUTLET J232
CB5 in 110/208 VAC
POWER DISTRIBUTION PANEL
DOES NOT
POWER
OPERATE IN
DISTRIBUTION PANEL
NORMAL MODE -
to see if it has
Continued
tripped.
2. If circuit breaker CB5 is
tripped, position to ON to
reset.
3. Position master power switch
to on (WP 0004 00).
4. If circuit breaker trips again,
notify Field Maintenance.
5. Position master power switch
to off (WP 0004 00).
6. Close door on 110/208 VAC
POWER DISTRIBUTION
PANEL.
0069 00-115
|