Click here to make tpub.com your Home Page

Page Title: Section Il. TROUBLESHOOTING
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 9-6115-663-13&P
Section Il. TROUBLESHOOTING
5-4. GENERAL.
Refer to TM 9-6115-645-24 for generator set troubleshooting procedures, and to TM 9-2815-256-24 for
engine troubleshooting procedures. Refer to TM 9-2330-205-14&P for trailer troubleshooting procedures.
The symptom index for the power plant lists faults associated with switch box assembly operation.
Figures 5-1 through 5-9 provide a go-no-go flowchart of each malfunction. Each malfunction listed
includes a reference to the applicable figure that contains a chart to help you determine probable causes
and corrective actions to take. The symptom index cannot list all faults that may occur, nor all the tests
or inspections and corrective actions. If a malfunction is not listed or cannot be corrected by listed
corrective actions, notify next higher level of maintenance for assistance.
SYMPTOM INDEX
Troubleshooting
Symptom
Procedure
Unit A STATUS lamp does not light with generator set AC CIRCUIT INTERRUPTER
switch closed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit A has no input power to K1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit A has no output power from K1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit A has output power from K1 but no output at one or more load terminals . . . . . . . . . . .
Unit B STATUS lamp does not light with generator set AC CIRCUIT INTERRUPTER
switch closed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit B has no input power to K2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit B has no output power from K2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Unit B has output power from K2 but no output at one or more load terminals . . . . . . . . . . .
Power cable W19 and paralleling cables are good, but unit fails to parallel through switch box

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business